Eaton B-Line series Type 1 junction boxes, 12" height, 4" length, 10" width, NEMA 1, Screw cover, SC NK enclosure, Surface mounted, Small single door, No knockout, Thru holes, Carbon steel
Manufacturer Resources
Product Specs
- Certifications:
- UL 50
- Country Of Origin:
- United States
- Cover Type:
- Screw
- Finish Color:
- Painted
- Mounting Hole Details:
- Thru holes
- Mounting Method:
- Surface
- Nema Rating:
- 1
- Product Height:
- 12 in
- Product Length Depth:
- 4 in
- Product Weight:
- 7.3 lb
- Product Width:
- 10 in
- Special Features:
- Keyhole slots on cover, plated screws
- Wall Thickness:
- 16 gauge
- Department:
- Electrical
- Product Model:
- SC NK enclosure
- Product Color:
- ANSI 61 Grey
- Product Style:
- Small single door
- Product Material:
- Carbon steel
- Product Length:
- 4 in
B-LINE 12104 SC NK – Frequently Asked Questions
1) Can a B-Line 12104 SC NK junction box be used outdoors or in a washdown area?
No. The 12104 SC NK is a NEMA Type 1 enclosure, which is indoor use only and offers no protection against rain, dust, or hosedown. For wet or outdoor locations you need a Type 3R, 4, or 4X box instead. Type 1 is fine for dry indoor electrical rooms, mechanical spaces, and above-ceiling junctions.
2) What are the actual box dimensions on the B-Line 12104 SC NK enclosure?
It measures 12 inches high, 10 inches wide, and 4 inches deep. The 4 inch depth is the number to check first if you are stacking terminal blocks or bringing in large conduit bodies, since it limits how much wire bending space you have behind the cover.
3) Does this B-Line junction box come with knockouts for conduit?
No knockouts. The 12104 SC NK is a no-knockout box, so every conduit entry has to be punched or hole-sawed in the field wherever your run lands. That is an advantage on a job where the conduit layout is not standard, but plan the labor for it. If you want factory knockouts, order the knockout version of the same size box rather than this NK model.
4) Is the 12104 SC NK junction box UL listed?
Yes, it carries UL 50 certification, the standard for enclosures for electrical equipment. That plus the Type 1 rating is generally what an inspector or a spec writer is looking for on an indoor junction box. It is also made in the US.
5) How does the cover come off on the 12104 SC NK, and can one person do it?
It is a screw cover with plated screws, and the cover has keyhole slots so you can back the screws out partway and lift the cover off without removing them completely, or rehang it one-handed while you start the screws. Practical difference versus a hinged door box: the screw cover is more tamper-resistant but slower to open, so use a hinged-door enclosure if you expect frequent access.
6) How does this B-Line box mount to a wall, and do I need extra hardware?
Surface mounting through thru holes in the back of the enclosure. You supply the anchors or fasteners to suit the substrate (concrete, block, stud, or Unistrut), since the box ships with the holes provided and no anchors. At 7.3 pounds empty it is a two-anchor-minimum wall hang for most substrates, more once it is full of conductors.
7) What gauge steel is the B-Line 12104 box, and will it match the other enclosures in my electrical room?
Carbon steel at 16 gauge, painted ANSI 61 grey. ANSI 61 is the standard grey used across most industrial control and junction enclosures, so it will read as a match next to typical panel and gutter finishes in the same room. The 16 gauge body holds its shape when you are drilling conduit entries and tightening bushings.
8) What is the exact part number to order for the B-Line 12x10x4 screw cover no-knockout box?
Eaton B-Line part number 12104 SC NK. The number reads as the dimensions first (12 high by 10 wide by 4 deep), then SC for screw cover and NK for no knockouts. Same B-Line numbering logic applies across the size range, so 12104 with a different suffix is the same box with a different cover or knockout arrangement.
9) Is a screw cover Type 1 box like this suitable as a pull box for feeder conduit, or do I need something else?
It works as a pull or junction box for indoor dry-location runs, and the no-knockout back and sides let you place entries exactly where the conduit lands. Where it falls short is depth: at 4 inches, large-diameter feeder conduit with angle pulls can run out of required bending space fast. For big feeders size the box off your conduit diameter and step up to a deeper enclosure rather than forcing it into this one.
How fast can I get the B-LINE 12104 SC NK delivered?
Most orders ship the same day from our distribution partners, with quick delivery throughout the
continental
U.S.
Need it urgently? Contact Us for expedited shipping options.
Can I return it if it doesn’t work for me?
Yes—ZenSupply offers a hassle-free return policy. If the product isn’t the right fit,
reach out to our support team for a return authorization or setup a return by following our return instructions.
Does the B-LINE 12104 SC NK come with a warranty?
Absolutely. The B-LINE 12104 SC NK is backed by a manufacturer’s warranty.
For full warranty terms, check the product documentation or Contact Us.
How do I get technical support or installation help for the B-LINE 12104 SC NK?
You can call, text, or email our expert support team for fast answers. We’re here to help with
product
selection,
installation tips, and troubleshooting. Contact Us
Why buy the B-LINE 12104 SC NK from ZenSupply?
ZenSupply makes it easy to get the commercial door hardware you need—fast shipping, expert support,
and
rewards on
every order.
Our team is always ready to help you choose the right product for your project.