Eaton A200 Overload Heater Coil for Size 3 & 4 Starters, 3-Phase
The Eaton A200 Overload Heater Coil is engineered for use with A200 Starter Sizes 3 and 4 on 3-phase-only applications, providing precise thermal overload protection for motor circuits. This NEMA-design heater is available in a Non-Compensated, Ambient A rating with a full load current range of 23.3-25.6A, and is compatible with Type A and B overload relays featuring both thermal and fast-trip response. Select the correct heater coil based on the full load current (FLA) shown on the motor nameplate to ensure proper protection.
Key Features
- Amperage Range: Non-Compensated, Ambient A rating of 23.3-25.6A for accurate motor overload sizing.
- Starter Compatibility: Designed for use with Eaton A200 Starter Sizes 3 and 4, 3-Phase only.
- Overload Relay Type: Compatible with Type A and Type B overload relays.
- Trip Type: Thermal and fast trip protection helps guard motors against sustained overcurrent and rapid fault conditions.
- Design Standard: NEMA design construction for reliable performance in industrial motor control applications.
- Sizing Guidance: Heater coils are rated to protect at a 40 degree C rise with a 1.15 service factor; three-phase applications require three heaters.
Technical Specifications
- Warranty: Eaton Selling Policy 25-000, one (1) year from the date of installation of the Product or eighteen (18) months from the date of shipment of the Product, whichever occurs first.
- Product Type: Motor Starter Heater Coil.
- Design: NEMA.
- Overload Relay: Type A and B.
- Type: A200 Heater.
- Trip Type: Thermal and fast trip.
- Used With: A200 Starter Sizes 3 & 4, 3-Phase Only.
Typical Applications
- Motor Control Centers and Starter Panels
- Three-Phase Motor Overload Protection
- Industrial and Commercial Motor Starter Retrofits
- A200 Series Starter Maintenance and Replacement
- Panelboard and Motor Control Wiring Systems
Why Eaton?
Eaton's A200 overload heater coils are built to NEMA design standards, delivering dependable thermal and fast-trip protection for Size 3 and 4 starters in demanding 3-phase motor control applications. Backed by Eaton's Selling Policy 25-000 warranty, these heater coils help ensure code-compliant, reliable motor protection for professional electrical installations.
Manufacturer Resources
Product Specs
- Product Design:
- NEMA
- Special features:
- Used with A200 Starter Sizes 3 & 4, 3-Phase Only
- Overload relay:
- Type A and B
- Product Type:
- A200 Heater
- Trip type:
- Thermal and fast trip
- Used with:
- Used with A200 Starter Sizes 3 & 4, 3-Phase Only
- Department:
- Electrical
- Amperage Rating:
- 23.3-25.6A
- Standards:
- NEMA
- Configuration:
- Thermal and Fast Trip
- Series:
- A200
- Product Group:
- Starters & Contactors