Eaton A200/B100 NEMA Overload ...
IN STOCK (leaves warehouse same day if ordered before 3pm ET)
$97.36

Eaton A200/B100 NEMA Overload Heater Element

(No reviews yet) Write a Review

Model: FH27

In Stock (leaves warehouse same day if ordered before 3pm ET)

$97.36
Adding to cart… The item has been added
Free Shipping on orders over $199
We price match and offer bulk discounts! Click Add to Quote. It's quick and easy.
✨
Earn points with this purchase! You can redeem points for giftcards, iPads, XBox's and more. View Rewards
Free Keying on all locks

Eaton A200/B100 NEMA Overload Heater Element

The Eaton A200/B100 Overload Heater Element is engineered for use with NEMA Starter Sizes 0, 1, and 2, providing precise thermal overload protection for motor control applications. This heater is rated for an ambient range of 2.59-2.83A, with a non-compensated rating of 2.40-2.63A and 2.93-3.21A, and is compatible with Type A and Type B overload relays. Featuring both thermal and fast trip response, this heater element delivers reliable, code-compliant overcurrent protection for NEMA-rated motor starters.

Key Features

  • Starter Compatibility: Designed for use with NEMA Starter Sizes 0, 1, and 2.
  • Overload Relay Type: Compatible with Type A and Type B overload relays for flexible application across Eaton starter platforms.
  • Ambient Rating: Rated 2.59-2.83A for standard ambient operating conditions.
  • Non-Compensated Rating: Rated 2.40-2.63A and 2.93-3.21A for non-compensated applications.
  • Trip Type: Thermal and fast trip response for dependable overcurrent protection.
  • Design Standard: Built to NEMA design specifications for motor control and protection systems.
  • Heater Series: A200/B100 heater series for consistent fit and performance in compatible Eaton starters.

Technical Specifications

  • Product Type: Motor Starter
  • Department: Electrical
  • Type: A200/B100 Heater
  • Overload Relay: Type A and B
  • Trip Type: Thermal and fast trip
  • Design: NEMA

Typical Applications

  • Motor Control Centers and Starter Panels
  • NEMA Size 0, 1, and 2 Motor Starter Replacement Parts
  • Overload Relay Maintenance and Retrofits
  • Commercial and Industrial Motor Control Installations
  • Panelboard and Motor Circuit Protection Upgrades

Why Eaton?

Eaton overload heater elements are manufactured to precise ambient and non-compensated current ratings, ensuring accurate thermal protection for NEMA-rated motor starters. With thermal and fast trip response built to NEMA design standards, this A200/B100 heater series delivers the dependable performance electrical professionals require for motor control and protection applications.

Manufacturer Resources

Product Specs

Product Type:
Overload Heater
Overload relay:
Type A and B
Trip type:
Thermal and fast trip
Product Design:
NEMA
Department:
Electrical
Series:
A200/B100
Standards:
NEMA
Product Group:
Wiring Devices

Eaton FH27 – Frequently Asked Questions

1) How do I pick the right Eaton FH heater element for my motor?
Pick by the motor's full load amps off the nameplate, then match it to the FH element whose FLA band contains that value. The A200/B100 range runs from .29-.31A (FH50) at the low end up through 23.0-25.2A (FH49), with steps like .97-1.06A (FH15), 3.00-3.28A (FH27), 6.3-6.8A (FH35), 12.0-13.1A (FH42) and 20.1-21.9A (FH48). The bands are narrow and do not overlap, so a motor drawing 8.0A takes the FH37 (7.6-8.2A), not the next size up.
2) Will an FH heater fit a NEMA Size 2 starter?
Yes. The Eaton A200/B100 FH heater elements are made for NEMA Starter Sizes 0, 1 and 2. If your starter is Size 3 or larger, this heater series is not the right part.
3) My motor nameplate reads 18.5 FLA. Which Eaton heater do I order?
The FH46 covers 17.3-18.9A, so an 18.5A motor falls in that band. Note that the neighbouring FH47 is 16.4-18.0A and FH45 is 15.8-17.2A, so the part numbers do not run in strict amperage order. Read the band, not the sequence.
4) Do Eaton FH heaters work with both Type A and Type B overload relays?
They do. The A200/B100 heater series is listed for use with Type A and Type B overload relays, so the same element covers both Eaton starter platforms rather than forcing a separate part number per relay type.
5) Can I use an FH heater element as a drop-in replacement in an existing motor control center?
That is the usual application. These are replacement heater elements for NEMA Size 0, 1 and 2 starters already installed in motor control centers and starter panels, used for overload relay maintenance and retrofits. Confirm the starter takes a Type A or Type B overload relay and order by the motor's FLA band, not by the number stamped on the old heater if the motor has since been changed.
6) Is one heater element enough, or do I need one per phase?
Heater elements are sized and sold individually by FLA band, and a three phase NEMA starter carries a heater in each pole. Order matching elements for every phase your overload relay is set up for, all from the same FLA band, so the trip point is consistent across poles.
7) What kind of trip response do these Eaton overload heaters give?
Thermal and fast trip. The element heats in proportion to motor current and trips the overload relay on a sustained overload, with a fast trip response for harder faults. It is a NEMA design part, so it follows NEMA motor control practice rather than an IEC class rating.
8) What is the smallest motor these Eaton heaters will protect?
The bottom of the range is the FH50 at .29-.31A, which suits very small fractional horsepower loads. The next steps up are the FH15 at .97-1.06A and FH16 at 1.07-1.16A, so there is a gap between roughly .31A and .97A in this heater group.
How fast can I get the Eaton FH27 delivered?
Most orders ship the same day from our distribution partners, with quick delivery throughout the continental U.S. Need it urgently? Contact Us for expedited shipping options.
Can I return it if it doesn’t work for me?
Yes—ZenSupply offers a hassle-free return policy. If the product isn’t the right fit, reach out to our support team for a return authorization or setup a return by following our return instructions.
Does the Eaton FH27 come with a warranty?
Absolutely. The Eaton FH27 is backed by a manufacturer’s warranty. For full warranty terms, check the product documentation or Contact Us.
How do I get technical support or installation help for the Eaton FH27?
You can call, text, or email our expert support team for fast answers. We’re here to help with product selection, installation tips, and troubleshooting. Contact Us
Why buy the Eaton FH27 from ZenSupply?
ZenSupply makes it easy to get the commercial door hardware you need—fast shipping, expert support, and rewards on every order. Our team is always ready to help you choose the right product for your project.