Eaton Type BR Three-Phase Main Lug Loadcenter with Aluminum Bus
Four-wire, three-phase Type BR main lug loadcenter with aluminum bus and standard neutral. Rated 10 kAIC at 208Y/120, 240V. Accepts Type BR 1-inch breakers. Available in 125A, 150A and 200A main ratings, 12 to 42 spaces, and indoor or outdoor enclosures. Cover included.
Key Features
- Three-phase, four-wire: Standard neutral for 208Y/120 and 240V systems.
- Aluminum bus: Main lug configuration with no feed-thru lugs.
- 10 kAIC interrupt rating.
- Type BR breaker compatibility: Uses Type BR 1-inch breakers.
- Cover included: Metallic enclosure with combination mounting.
- Hold-down screw: Includes BREQS125 hold-down screw.
Technical Specifications
- Bus Material: Aluminum
- Cover Type: Cover included
- Enclosure Material: Metallic
- Interrupt Rating: 10 kAIC
- Main Circuit Breaker: BR
- Mounting Method: Combination
- Number Of Wires: 4
- Phase: Three-phase
- Product Details: Main lug
- Special Features: No feed-thru lugs, includes BREQS125 hold-down screw
- Used With: Type BR 1-inch breakers
- Voltage Rating: 208Y/120, 240V
- Wire Size: #6-2/0 AWG Cu/Al
Variant Specifications
| Amperage | Main Ampere Rating | Spaces | Box Size Option | Enclosure Option | SKU |
|---|---|---|---|---|---|
| 125A | 125A | 12 | C1 | Indoor | 3BR1224L125 |
| 125A | 125A | 12 | C1R | Outdoor | 3BR1224L125R |
| 200A | 200A | 12 | C4 | Indoor | 3BR1224L200 |
| 200A | 200A | 12 | C3R | Outdoor | 3BR1224L200R |
| 150A | 150A | 18 | C2 | Indoor | 3BR1836L150 |
| 150A | 150A | 18 | C3R | Outdoor | 3BR1836L150R |
| 200A | 200A | 18 | C4 | Indoor | 3BR1836L200 |
| 200A | 200A | 18 | C3R | Outdoor | 3BR1836L200R |
| 150A | 150A | 24 | D1 | Indoor | 3BR2442L150 |
| 150A | 150A | 24 | D1R | Outdoor | 3BR2442L150R |
| 200A | 200A | 30 | G1 | Indoor | 3BR3042L200 |
| 200A | 200A | 30 | G1R | Outdoor | 3BR3042L200R |
| 200A | 200A | 42 | L1 | Indoor | 3BR4242L200 |
| 200A | 200A | 42 | L1R | Outdoor | 3BR4242L200R |
Manufacturer Resources
Product Specs
- Enclosure Material:
- Metallic
- Cover Type:
- Cover included
- Voltage Rating:
- 208Y/120, 240V
- Number Of Wires:
- 4
- Product Type:
- Load Center
- Bus Material:
- Aluminum
- Phase:
- Three-phase
- Used With:
- Type BR 1-inch breakers
- Product Details:
- Main lug
- Product Group:
- Power Distribution
- Department:
- Electrical
- Mounting Method:
- Combination
- Product Subgroup:
- Panelboards & Load Centers
Eaton 3BR1224L125 – Frequently Asked Questions
1) Will an Eaton Type BR three-phase main lug loadcenter work on a 208Y/120 volt commercial service?
That is exactly the service it is built for. The BR three-phase main lug loadcenter is rated 208Y/120 and 240V, four-wire, so it takes the three phase conductors plus a neutral off a wye service and gives you 120V line-to-neutral for receptacles and lighting alongside 208V three-phase for motors and equipment. If your building is a 480Y/277 service, this is the wrong panel.
2) What size feeder wire lands in the main lugs on the Eaton 3BR three-phase loadcenter?
The lugs accept #6 through 2/0 AWG, copper or aluminum. That covers the feeder range from the 125A version up through the 200A versions. Bus is aluminum, so use the appropriate antioxidant compound and torque per the label when landing aluminum conductors.
3) Can I use this Eaton loadcenter as service equipment, or do I need a main breaker panel?
It is a main lug panel, so there is no main breaker in it. Eaton lists it as suitable for use as service equipment when no more than six main disconnecting means are provided. In practice that means either you feed it downstream of a separate service disconnect, or you use the six-throw rule with breakers in the panel itself. If the job calls for a single main disconnect at the panel, you need a main breaker loadcenter instead of this one.
4) Which breakers fit an Eaton 3BR three-phase loadcenter?
Type BR 1-inch breakers. That is Eaton's plug-on BR line, one inch per pole, and for three-phase branch circuits you use BR two-pole and three-pole breakers on the appropriate phase positions. Square D Homeline, QO, and Siemens breakers do not belong in this panel.
5) Is there an outdoor rated version of the Eaton 3BR three-phase main lug loadcenter?
Yes. Every space count comes in both an indoor and an outdoor enclosure, and the outdoor catalog numbers carry an R suffix: 3BR1224L125R and 3BR1224L200R at 12 spaces, 3BR1836L150R and 3BR1836L200R at 18, 3BR2442L150R at 24, 3BR3042L200R at 30, and 3BR4242L200R at 42. Enclosure is metallic either way, and the cover is included.
6) How many three-phase circuits can I actually get out of a 42-space BR loadcenter?
Spaces are counted in single-pole positions, and a three-phase branch circuit eats three of them. So the 42-space 3BR4242L200 gives you fourteen three-pole circuits if every load is three-phase, or any mix you like of three-pole, two-pole and single-pole 120V circuits off the neutral. The range runs 12, 18, 24, 30 and 42 spaces. Size the panel by the poles you need plus spares, not by circuit count on the drawing.
7) Can I feed a second panel through an Eaton 3BR three-phase main lug loadcenter?
Not through feed-thru lugs. These panels have no feed-thru lugs, so you cannot land a second set of feeder conductors on the far end of the bus to carry power onward. To feed a downstream panel, install a three-pole BR breaker in a branch position and take the feeder from there.
8) Can I surface mount this Eaton loadcenter, or does it have to go in the wall?
Either. The mounting method is combination, meaning the same enclosure can be flush mounted in a wall or surface mounted on it. On the outdoor R versions you are surface mounting in practice. Cover comes with the panel.
9) Do I need to buy anything extra to install breakers in a BR three-phase loadcenter?
The hold-down screw is already in the box. Eaton ships a BREQS125 hold-down screw with the panel, which is what secures breakers where the installation requires it. Beyond that you supply the BR branch breakers, the feeder conductors and the fittings. Cover and enclosure are included.
10) I need a 200 amp three-phase panel for a restaurant. Which Eaton 3BR catalog number do I order?
At 200A the choice is space count and enclosure. Indoor: 3BR1224L200 with 12 spaces, 3BR1836L200 with 18, 3BR3042L200 with 30, 3BR4242L200 with 42. Outdoor: 3BR1224L200R, 3BR1836L200R, 3BR3042L200R, 3BR4242L200R. For a restaurant with three-phase kitchen equipment plus 120V lighting and receptacle circuits, count poles first, since every three-phase load takes three spaces, then add spares before you pick.
11) Will this Eaton panel run single-phase 120 volt circuits too, or only three-phase loads?
Both. Because it is a four-wire panel with a standard neutral on a 208Y/120 system, single-pole BR breakers give you 120V circuits for lighting and receptacles, two-pole gives 208V, and three-pole gives full three-phase. That mix is the normal case in an office or retail buildout where the HVAC is three-phase and everything else is not.
12) What is the smallest Eaton three-phase main lug loadcenter available, for a small tenant space?
The 125A, 12-space version is the entry point: 3BR1224L125 indoor or 3BR1224L125R outdoor. Twelve single-pole spaces is four three-phase circuits if all loads are three-phase, so it suits a small tenant suite or a subpanel serving a handful of pieces of equipment. If you need more than 125A of feeder capacity in that same 12-space footprint, the 200A 3BR1224L200 gives you the higher rating at the same space count.
13) Aluminum bus versus copper bus in a loadcenter, does it matter for a commercial job?
The BR three-phase loadcenter uses an aluminum bus. Aluminum bus is the standard on loadcenters at this class and carries the panel's full rating, 125A, 150A or 200A depending on the version. Where a specification on the drawings explicitly calls out copper bus, this panel will not satisfy it and you want a copper bus panelboard instead. Otherwise it is a non-issue.
How fast can I get the Eaton 3BR1224L125 delivered?
Most orders ship the same day from our distribution partners, with quick delivery throughout the
continental
U.S.
Need it urgently? Contact Us for expedited shipping options.
Can I return it if it doesn’t work for me?
Yes—ZenSupply offers a hassle-free return policy. If the product isn’t the right fit,
reach out to our support team for a return authorization or setup a return by following our return instructions.
Does the Eaton 3BR1224L125 come with a warranty?
Absolutely. The Eaton 3BR1224L125 is backed by a manufacturer’s warranty.
For full warranty terms, check the product documentation or Contact Us.
How do I get technical support or installation help for the Eaton 3BR1224L125?
You can call, text, or email our expert support team for fast answers. We’re here to help with
product
selection,
installation tips, and troubleshooting. Contact Us
Why buy the Eaton 3BR1224L125 from ZenSupply?
ZenSupply makes it easy to get the commercial door hardware you need—fast shipping, expert support,
and
rewards on
every order.
Our team is always ready to help you choose the right product for your project.